Xitanium SR Bridge
Prices are currently being updated on the website, please contact the office for any price enquiries.
The Xitanium SR bridge helps you reduce the cost and complexity of light fixtures in wireless connected lighting systems.
Two versions of the Xitanium SR bridge are available; a built-in type for integrating into a luminaire, and a stand-alone model for external mounting. Both have a full SR interface with sensor power supply, energy metering and diagnostics. A relay prevents standby power levels becoming too high when multiple drivers are connected.
Product Description
Mains input range The Xitanium SR Bridge can operate on mains input voltages from 220Vac – 240Vac.
Switchable Output using Zero Crossing detection The Output of the Xitanium SR Bridge can be switched on/ off using relay switching with Advanced Zero Crossing technology. This allows for higher loads to be switched on/off.
- Note: The relay can be switched off and DALI off command can be used instead. The Philips MultiOne software can be used for configuration.
- Note: For DALI, Identification, SET POWER ON LEVEL command cannot stop the identification blinking mechanism immediately.
Programmable Interface The Xitanium SR Bridges are programmable. A number of features and parameters can be set via either MultiOne Configurator or SimpleSet. Items that can be programmed are: AOC & Fault detection.
SR (Sensor Ready) interface The Xitanium SR Bridge features a digital interface (SR interface) to enable direct connection to any suitable SR (certified) RF sensor.
Energy metering The Xitanium SR Bridge has built in Energy/power measurement capability.
Multiple Drivers on a Single SR Bridge More than one driver can be connected to a SR bridge. The details can be found in the datasheet of the SR bridge that can be downloaded at www.Philips.com/Technology.
A Single EasyAir sensor Connected to Multiple SR Bridges As with SR drivers, it is possible to use one sensor to control multiple luminaires. When EasyAir is connected to multiple Philips Xitanium SR Bridges (and drivers), the maximum number of connected bridges (and drivers) is 10 and only four can have enabled DALI power supply. To minimize unnecessary losses, it is recommended to turn on only two DALI power supplies. Each SR bridge (and driver) provides approximately 55 mA of current on the DALI bus, and EasyAir is limited to 250 mA.